Experimental Study of the Condensation Heat Transfer Performance of Flue Gases in a Heating-and-power Cogeneration System

赵玺灵,付林,张世钢,杨巍巍
2009-01-01
Abstract:Concerning the problem of the inability to fully recover the waste heat in flue gases,experimentally studied was a flue gas condensation heat recovery device of an innovative heating-and-power cogeneration system that could fully recover the waste heat in flue gases.In this connection,the research emphasis was laid on the heat transfer performance of a smooth tube flue-gas condensing equipment item under the relevant operating condition.The research results indicate that under the test operating condition,the heat transfer coefficient of the dry type condensing section can be as high as 60 W/(m2·K) with that of the condensing section being 90 to 100 W/(m2·K).The heat transfer coefficient of the condensing section is about 1.5 to 1.7 times that of the dry type one.The authors have also worked out a heat transfer criterion-based relational expression under the operating condition,thus providing an underlying basis for popularizing the design and operation of the system in question.
What problem does this paper attempt to address?