Study on Upgrading and Reconstruction of Oxidation Ditch Process in Sewage Treatment Plant
ZHANG Jing-yu,WANG Shu-ying,HOU Hong-xun,ZHANG Hui,PENG Yong-zhen,GAO Yong-qing
DOI: https://doi.org/10.19853/j.zgjsps.1000-4602.2011.07.003
2011-01-01
Abstract:The oxidation ditch process adopted in a sewage treatment plant needed upgrading and reconstruction.The experimental study was done by plug flow reactor to reduce risk,and the feasibility analysis was carried out.The results show the nitrification effect is improved by adding anoxic zone,but the denitrification effect is not improved significantly,meanwhile,phosphorus removal efficiency is decreased.The reason of improving of nitrification effect is that the removal rate of organic matter by aerating is low,which is 0.6 mg/(gSS·min).When adding anoxic zone,organic matter is removed mostly by denitrification,the removal rate is 1.8 mg/(gSS·min),so nitrification time is increased,and nitrification effect is improved.When anoxic zone is not set,denitrification and phosphorus release can occur in the mixed zone because of low DO,and good denitrification and phosphorus removal effect are achieved.When adding anoxic zone,denitrification environment is enhanced,competitive ability of PAOs for carbon source is reduced,so denitrification effect is improved slightly,and phosphorus removal efficiency is decreased.According to the experimental result,it is advised that the first surface aerating machine of the oxidation ditch can be replaced by submersible water impellers,and the effluent quality can basically meet the first level A discharge standard.