An experimental study on the thermal and hydraulic characteristics of the corrugated plate air-cooled heat exchanger

Xu Wangfa,Zhang Xu,Luo Haiyan
DOI: https://doi.org/10.16711/j.1001-7100.2007.02.014
2007-01-01
Abstract:Experiments of heat transfer and pressure drop in a corrugated plate air-cooled heat exchanger were conducted with variable supply air and hot water flow rates.Both air-side pressure drop correlations and air-side and water-side heat transfer coefficients were obtained,where the Reynolds number for water side ranged from 2000 to 8000 and the Reynolds number for air side ranged from 2000 to 10000.Furthermore the performances of heat transfers including corrugate plate,tube and fin-tube were compared under the same conditions.The results show that when the air frontal velocity is between 2.45 and 4.1 m/s,the overall heat-transfer coefficient of plate heat exchanger ranges from 100 to 160 W/m~2/℃ equal to one sixth of that of fin-tube cooler based on tube outside area,which is about 70% higher than that of tube cooler.The volumetric heat transfer capacity of plate cooler is 1.5 times as that of fin-tube cooler and 15 times as that of tube cooler.The heat transfer capacity of per unit power of plate cooler is 5.5 times as that of tube cooler and similar results for fin-tube cooler.