Abstract:To maximize the use of resources,it is necessary to set adjacent commercial areas next to the transfer hall in integrated transport hub.The existence of numerous combustible causes great fire risk in commercial areas.In order to meet the requirements of the high permeability,a large number of fire shutters have been used between adjacent commercial areas and transfer hall to prevent fire spreading.However,the reliability of fire shutter is not high,so provisions used to limit the use proportion of fire shutters were introduced in different parts of country.These bring some difficulties to set adjacent commercial areas in integrated transport hub.By taking an example of transfer hall in a transport hub,using performance-based analysis method,and setting different fire shutter width ratio,effects of commercial fire to personnel safety in transfer hall were demonstrated in the paper.With certain fire safety measures,it is concluded that setting ratio of fire shutter in the total separation width between adjacent commercial areas and transfer hall in integrated transport hub can be added to 40% for the example in this paper.
What problem does this paper attempt to address?