Reconsideration of the Selection of Stator Winding Type for Large-sized Hydraulic Generator with Low Rotational Speed

GUI Lin,DUO Liang,YANG Zhongguo,QIU Erui,WANG Xiangheng
DOI: https://doi.org/10.3969/j.issn.1000-3983.2013.04.009
2013-01-01
Abstract:For restraining the generator’s vibration attributed to rator eccentricity,lap winding or centralized arrangement wave winding is adopted by a series of slow-speed large-sized hydraulic generators recently,but their main protection performance are probably harmful to the generators’ safe operation.By using the quantitative and optimum design methods of main protection for large-sized hydraulic generator of Xiluodu,Liyuan and Guanyinyan power stations,main protection performance of slow-speed large-sized hydraulic generators with different stator winding types are analyzed and compared based on the quantitative analysis.New suggestions on stator winding design of large-sized hydraulic generator are presented in this paper.Selecting centralized arrangement wave winding for the large-sized hydraulic generator with low rotational speed can meet the requirements of electric machine design and relaying protection simultaneously.At the time of restraining the generator’s vibration attributed to rator eccentricity,above stator winding type may not lead to the remarkable increase of non-operation fault number of main protection.
What problem does this paper attempt to address?