Influence of Opening and Closing Resistor of Disconnecting Switches to VFTO in 750 Kv GIS

余芳,贾磊,周春雨,郭洁
DOI: https://doi.org/10.16188/j.isa.1003-8337.2008.04.008
2008-01-01
Abstract:The application of gas insulated substation(GIS) has expended year by year, Harm of the very fast transient voltages (VFTO) caused during disconnecting switches (DS) operation becomes more obvious. This paper refers to 750 kV GIS of Guanting substation in northwest China power system. With the electro-magnetic transient program(EMTP), the VFTO under 40 operation models was simulated and calculated. According to different models of DS, the effect of opening and closing resistor was analyzed. Compared with the results of DS without resistor, the amplitude and steepness of VFTO decreased by 50% and 14%.The highest frequency of component with voltage above 1 kV reduced to 10%.