Experimental Investigation on Imbalance Heat Load of the Two-phase Dual-Evaporator Cooling System

LIU Jie,GUO Kai-hua,HE Zhen-hui,LV Mou
2008-01-01
Abstract:A brief review of the two-phase cooling loop driven by mechanical pump is presented,and a proposed experimental system with dual-Evaporator by using CO2 as the working fluid is described.In order to apply this technology for the thermal control systems,tests have been performed to clearly comprehend its performance under cyclic temperature changing.Special attention has been paid to the heat rejection characteristics under unbalance heat load on the dual-Evaporator.From the experiments,it demonstrates that when heat load unbalance happens,the mass flow distribution between two branch has changed,the higher heat load is,the smaller mass flow is gotten.At last the mass flow would gasify completely and temperature at the outlet of a higher heat load branch would enhance.Meanwhile,decreasing heat load difference is benefit for the mass flow equalization and is an effective means for the evaporative stability.In a word,the two-phase Mechanical Pumped Cooling System with dual-Evaporator has more advantages than capillary pump cooling loop not only on the heat rejection capacity and isothermal characteristic but also on dealing with unbalance heat load.