Experiment Investigation on a Honeycomb Micro-channel Based Cooling System

CHENG Ting,LUO Xiao-bing,HUANG Su-yi,LIU Sheng
DOI: https://doi.org/10.3969/j.issn.1001-5868.2007.06.019
2007-01-01
Abstract:Heat dissipation by micro-channel heat sink provides a kind of new solution for thermal management.A kind of honeycomb micro-channel heat sink used for building a heat dissipation system is discussed.Experiments on such a system were conducted.The results demonstrate that with 13.3ml/s flow rate and room temperature of 32℃,the 17cm2 micro-channel heat sink can take out 233.63W heat,the corresponding heat flux of heat source is about 13.3W/cm2,in such a case,the temperature of the water inside the micro-channel heat sink is just about 52℃.It is also found that in order to take full advantage of micro-channel heat sink,without good heat exchange between system and environment for mini heat exchanger in present system,the micro-channel heat sink can not achieve good cooling effect.
What problem does this paper attempt to address?