Thermal Performance Study on Modular Evaporative Cooling Sandwich Wall on Mechanical Ventilation Condition

XU Peng,ZHAO Jia-jing,LI Jun-ming
DOI: https://doi.org/10.3969/j.issn.1006-7930.2011.04.016
2011-01-01
Abstract:To improve the wall insulation in summer,the thermal performance of a new modular evaporative cooling ventilated wall was studied on mechanical ventilation condition.Analyzing the flow and heat transfer conditions in air domain and water domain in the wall,appropriate mathematical model was found.Through CFD analyzing with Fluent,the law,which the main factors influence the heat-insulating performance of the wall,was found and the optimum structural parameters were obtained.It shows that the structure with water layer outside air layer is not suitable for mechanical ventilation and it has only limited energy saving potential.The sandwich wall with air layer outside water layer shows great advantage in heat-insulating performance.The wall with water layer thickness of 1cm and air layer thickness of 2 cm represents excellent heat-insulating performance and occupies small building space.The evaporative cooling sandwich wall with mechanical ventilation is a promising way to improve the building energy efficiency.
What problem does this paper attempt to address?