Effects of temperature and dissolved oxygen on biological activated carbon treating drainage from steel and iron industry

TANG Wen-wei,WANG Zhen-zhen,XU Jing-cheng,HUANG Xiang-feng
DOI: https://doi.org/10.3969/j.issn.1009-2455.2008.02.009
2008-01-01
Abstract:The effects of temperature and dissolved oxygen on biological activated carbon treating drainage from iron and steel industry was studied.the results showed that: the effect of biological activated carbon on pollutants removal was good,the average removal rates of turbidity,COD,ammonia nitrogen,iron and manganese were 78.7%、38.3%、82.6%、70.1% and 75.7% respectively at 20-25 ℃,and the removal rate decreased with temperature descending,especially when the water temperature was lower than 15 ℃,the average removal rate decreased obviously.Increasing DO properly could improve the effect of biological activated carbon on COD and ammonia nitrogen removal,however,the impact to the removal of Fe and Mn was not great.The DO of the influent water should be controlled in 5-6 mg/L,which was lower than the theoretical oxygen requirement 7.68 mg/L.
What problem does this paper attempt to address?