Experimental Study of Grid Ceiling Effect on Fire Control Efficiency of Automatic Sprinkler

Bing GAO,Bin YAO
DOI: https://doi.org/10.3969/j.issn.1004-5309.2008.04.008
2008-01-01
Fire Safety Science
Abstract:Automatic Sprinkler System is a regular automatic fire extinguishing system generally used.In this paper,the fire control efficiency of sprinkler with grid ceiling installed below was studied experimentally.Burning time was used to assess the fire control efficiency.The results indicate: grid ceiling affects the water distribution significantly,relating with installation height of sprinkler head and water pressure.The effect of grid ceiling can be reduced and the fire control efficiency can be improved by increasing water pressure and water flow rate.For a certain grid ceiling,there exists a poor installation height for sprinkler head to get bad performance.The research results can be used in practical project to keep the fire control efficiency of sprinkler when installed above grid ceiling.
What problem does this paper attempt to address?