Experimental Study on Pool Fire Suppression with Water Mist under Different Mechanical Ventilation Conditions

7HANG Xiao-nan,WANG Xi-shi,ZHOU Yang,TAO Chang-fa
DOI: https://doi.org/10.3969/j.issn.1671-8097.2011.03.011
2011-01-01
Journal of Thermal Science and Technology
Abstract:Based on full-scale experimental simulation,the smoke characteristics under applications of water mist and mechanical ventilation were studied.The wind flux and speed were adjusted through changing of the transducer frequency,while the position and size of smoke vent were changed through blocking,then the temperature and CO concentration under applications of water mist and mechanical ventilation were tested and analyzed.The results show that,with increase of smoke ventilation intensity,the fire extinction time with water mist becomes longer,while the mean temperature rise rate and the CO concentration reduces.The position of smoke exhaust has evident effects on fire extinguishing with water mist in the test cases.Key wrods: water mist;pool fire;mechanical smoke exhaust;smoke exhaust rate;fire suppression
What problem does this paper attempt to address?