Critical Condition of Pool Fire Suppression by Water Mist

HUANG Xin,LIU Jiang-hong,LIAO Guang-xuan,LU Qiang
DOI: https://doi.org/10.3321/j.issn:1006-8740.2006.04.008
2006-01-01
Abstract:In laboratory-scale experiments it is found that there are two different fire extinguishing processes owing to the variation of parameter of water mist.Then the critical value is obtained,which is necessary for water mist fire suppression by flame cooling,and validated by the laboratory-scale experiments and full-scale experiments.In experiments it is also found that the ability of penetrating smoke plume of mist is a crucial factor to the fire suppression.A ratio of smoke plume thrust to the mist spray thrust is introduced here,and the ratio is estimated as 10 by experiments.
What problem does this paper attempt to address?