Experimental and numerical study on water mist suppression system on room fire

Peizhong Yang,Tao Liu,Xian Qin
DOI: https://doi.org/10.1016/j.buildenv.2010.04.017
IF: 7.093
2010-01-01
Building and Environment
Abstract:Full-scale experiment and numerical simulations are carried out on a room fire to study water mist suppression system with heat release rate of 6 MW. A computational fluid dynamics (CFD) model of fire-driven fluid flow, FDS (Fire Dynamics Simulator), is used to solve numerically a form of the Navier–Stokes equations for fire. A fire experiment without water mist is performed and the temperatures are measured to validate the predictions of FDS code against the experimental data. Then a fire experiment with water mist suppression system is performed and the temperatures and extinguishing time are measured. The validated numerical model is used to simulate the experiment; the temperatures, oxygen concentration and extinguishing time are compared and studied. In numerical simulations, the cell size sensitivity is analyzed. The experimental results of temperatures and extinguishing time are compared with the results of numerical simulations. It appears that the numerical results are in good agreement (qualitatively) with the experimental data in temperature fields. These useful data can be helpful in accomplishing the design of water mist suppression system and the design regulations for fire safety management.
What problem does this paper attempt to address?