Abstract:HVDC transmission system who works in monopolar operation will generate neutral current that causes transformer DC bias,which will cause transformer local overheating,and increase the vibration,noise and other adverse reactions.The study situation of three main suppression methods of neutral current flowing to the transformer is analyzed,that is,series capacitance,connecting dynamic compensation device and series resistance.The series resistance method is simple,practical,economical and easy to promote the application in AC system near DC grounding electrode.It is pointed out that the aim is no limit exceeding of the DC value of the whole transformer neutral in AC grids,and the rational configuration by connecting the resistor is also proposed.In addition,the optimization design of transformer internal structure and a number of DC transmission lines sharing the same grounding electrode can suppress DC bias.The progress and the existing problems of relevant study are discussed.
What problem does this paper attempt to address?