Transformer Neutral Series Low Resistance Designed against DC Magnetic Bias

QIU Qiu,WU Guang-ning,REN Zhi-chao,ZHANG Yi-kun
2012-01-01
Abstract:When HVDC system works in monopolar or bipolar asymmetric ground mode,enormous DC earth-fault current leads to the ground potential rising around AC substation nearby,which results in DC invasion into the AC transformer with neutral grounding,then the generated DC magnetic bias may affect the normal performance of transformer.Therefore,this paper proposes a scheme to use neutral series low resistance to restrain the DC magnetic bias.PSCAD/EMTDC was adopted to model the AC power grid connected with resistors;the restraint effect was simulated;the influence of frequent overvoltage and lightning impulse overvoltage on transformer neutral insulation was analyzed;the value of series resistance was recommended.It is shown that transformer neutral series low resistance can restrain DC bias current simply and effectively.With the increase of resistance,the decay effect of current is not obvious.The series resistor will upgrade the voltage of neutral point in case of fault,so the value of low resistance is recommended to stand the short-time frequent overvoltage and impulse overvoltage,thereby the transformer neutral insulation will not be affected.