Enhanced and precise traveling wave fault location accuracy on transmission lines utilizing dual time of arrival
Nuradeen Aisar,Ruikun Mai,Wang Jungang,Anand Mal Lodha
DOI: https://doi.org/10.1007/s00202-024-02832-8
IF: 1.63
2024-11-16
Electrical Engineering
Abstract:This paper introduces an improved and precise two-end traveling wave-based fault location method on a transmission line which eliminates the need for both traveling wave velocity (TWV) and line parameters measurements. It relies solely on the arrival times of the fault current traveling wave for FL estimation in the two ends of the power system. Additionally, the method can estimate the TWV itself with high accuracy (up to 99.6%). Extensive simulations using PSCAD/EMTDC software on a 400 kV, 50 Hz, 300 km transmission line demonstrate the method's effectiveness, and the results obtained show high accuracy in fault distance estimation, with a maximum error of 0.03% for faults occurring within 140 km. Furthermore, the method performs well under various fault conditions, including high-resistance fault, varying fault inception angles, and even with noise present in the data. It was also validated on the WSCC 9-bus system, demonstrating rapid computational speed and robustness under varying operating conditions. The paper also discusses a technique to handle a system with a series compensation without compromising the algorithms performance. This method executes quickly, allowing for swift FL, while still maintaining high accuracy even when dealing with diverse operational conditions.
engineering, electrical & electronic