An Incremental Negative Sequence Admittance Method for Fault Detection in Inverter-Based Microgrids

Kwasi Opoku,Subash Pokharel,Aleksandar Dimitrovski
DOI: https://doi.org/10.48550/arXiv.2205.02962
2022-05-06
Abstract:Superimposed sequence quantities have been relied on for years to provide pure fault components for various applications in protection schemes. In more recent times, they have been employed in various solutions to the challenges introduced by integration of distributed generation in distribution systems. To improve the overall reliability of protection schemes deployed in such active distribution networks, this paper evaluates a new approach for detecting unbalanced faults using negative sequence quantities. A proposed superimposed negative sequence admittance element is validated using simulation tests on a modelled community microgrid. The performance of the method is tested for various fault scenarios in MATLAB/Simulink.
Systems and Control
What problem does this paper attempt to address?