Individual Sequence Control of DSTATCOM Compensation for Unbalanced Load

YANG Kun,CHEN Lei,CHEN Guozhu
DOI: https://doi.org/10.3969/j.issn.1006-6047.2012.07.007
2012-01-01
Abstract:The equivalent circuit of each sequence is analyzed for unbalanced load,the mathematical model of DSTATCOM in each sequence is established and the individual sequence control is proposed.For the positive and negative sequence components of load current are symmetry in three phases,they are compensated in the synchronous rotating coordinates system of positive and negative sequence respectively,while the zero sequence component is compensated in the three-phase coordinates system.The repetitive control is introduced to improve the compensation accuracy and suppress the low-order harmonics and disturbances.A 10 Mvar/10 kV DSTATCOM simulation system is built in MATLAB/Simulink and the results show the effectiveness of the proposed control strategy of compensation for unbalanced load and its ability in the grid voltage imbalance suppression.