Wind-induced ventilation rate of single-sided ventilation in a building with internal partition
Zitao Jiang,Tomohiro Kobayashi,Toshio Yamanaka,Mats Sandberg,Narae Choi,Noriaki Kobayashi,Kayuki Sano,Kota Toyosawa,Zitao JiangTomohiro KobayashiToshio YamanakaMats SandbergNarae ChoiNoriaki KobayashiKayuki SanoKota Toyosawaa Department of Architectural Engineering,Graduate School of Engineering,Osaka University,Osaka,Japanb Department of Building Engineering,Energy Systems and Sustainability Science,University of Gävle,Gävle,Swedenc Department of Architecture,Faculty of Science and Engineering,Toyo University,Tokyo,JapanZitao Jiang,PhD student supervised by Tomohiro Kobayashi at Osaka University,with interests in natural ventilation,city ventilation and wind engineering.Tomohiro Kobayashi,PhD,Professor at Osaka University. His research interests include natural ventilation,mechanical ventilation and ventilation theory.Toshio Yamanaka,PhD,Professor at Osaka University.Mats Sandberg,PhD,Senior professor at the University of Gävle. He's interested in indoor and urban environments with a focus on climate and ventilation.Narae Choi,PhD,Assistant Professor at Toyo University.Noriaki Kobayashi,technical staff at Osaka University.Kayuki Sano,master course student at Osaka University.Kota Toyosawa,master course student at Osaka University.
DOI: https://doi.org/10.1080/14733315.2024.2319475
2024-02-22
International Journal of Ventilation
Abstract:Wind-induced single-sided ventilation is a prevalent form of natural ventilation extensively used in buildings. Nevertheless, prior experimental investigations predominantly focused on single-zone buildings, neglecting the multizone buildings with internal partitions which is representative of more common scenarios. This study addresses this gap by investigating the impact of internal partitions on single-sided ventilation, employing a combination of wind tunnel experiment and numerical analysis. Airflow rate (AFR) was measured with a split-fibre probe and purging flow rate (PFR) was assessed by the tracer gas methodology. The PFR exhibits greater sensitivity to internal partitions in unidirectional airflow compared to bidirectional flow. Large Eddy Simulation (LES) was conducted to elucidate the intricate airflow characteristics in single-sided ventilation. The ventilation efficiency (ratio of PFR and AFR) derived from LES ranges between 0.74 and 0.79, which means that <80% of the AFR actively contributes to the removal of contaminants. Notably, the investigation discerned that the AFR of a single room approximates that of the entire room, whereas the PFR of a single room is smaller than that of the whole room. The disparities in AFR and PFR were caused by the recirculating flow, which was elaborated by the theoretical analysis.
energy & fuels,construction & building technology