Wind Tunnel Experimental Study on Single Room Ventilation Affected by Miscellaneous Factors

CHEN Yong,WANG Xu,SUN Bing-nan,LI Qing-xiang,CHEN Shui-fu
DOI: https://doi.org/10.3785/j.issn.1008-973x.2012.04.013
2012-01-01
Abstract:For single room,wind-driven ventilation is affected by miscellaneous factors simultaneously.The impact of wall porosity,the pressure difference between windward and leeward,area ratio of inlet to outlet and the relative position of windows on windward and leeward was analyzed through a series of wind tunnel experiments in association with numerical simulation.Then the empirical formula that described the relationship among the flow rate,wall porosity,and wind pressure difference was achieved.New parameter was involved in the formula to consider influence of inlet and outlet area ratio and the relative position of indoors on windward and leeward.Results show that flow rate rises proportionally to windward wall porosity and it becomes larger with the increase of wind pressure difference.If the total wall porosity is constant,the smaller the difference between the inlet and outlet area is the better ventilation can be attained.