Failure analysis of dry-type power transformer

D. Paul
DOI: https://doi.org/10.1109/28.924746
IF: 4.079
2001-01-01
IEEE Transactions on Industry Applications
Abstract:This paper provides the failure analysis of a three-phase, dry-type, silicone resin vacuum-pressure encapsulated, 750/1000-kVA, AA/FA, 34.5-kV–480 Y/277-V, delta–wye power transformer. Transient overvoltage switching surge propagation through the transformer winding and protection margin is discussed. An arbitrary sensitivity of 10 pC at 120% rated voltage generally used for the partial discharge tests at the factory may be inadequate for the design of the failed transformer.