Test Station for High Temperature Superconducting Power Cables

L. Quval,D. Huchet,F. Trillaud,M. Kiuchi,T. Matsushita,L. Quéval
DOI: https://doi.org/10.1109/tasc.2024.3360931
IF: 1.9489
2024-05-01
IEEE Transactions on Applied Superconductivity
Abstract:The Gargantua test station is capable of delivering a direct current of 4800 A at a voltage of 10 V. It is designed for acquiring the dc voltage-current characteristic of high-temperature superconducting power cables operating at 77.3 K in liquid nitrogen. The goal is to estimate their critical current. The standardization of this dc characterization is a prerequisite for the adoption of this promising technology by power grid operators. This document reports on the experimental setup and the subsequent measurements carried out on a high-temperature superconducting power cable manufactured by Sumitomo and tested as part of the international round robin test for the IEC Technical Committee 90 Superconductivity.
physics, applied,engineering, electrical & electronic
What problem does this paper attempt to address?