Survey of design energy efficiency ratio of air conditioning systems for hotel buildings in Chongqing
Lin Zhenguo,Zhang Suyun,Fu Xiangzhao,Xiao Yimin,Yang Lining
DOI: https://doi.org/10.3969/j.issn.1002-8501.2009.02.007
2009-01-01
Abstract:Surveys the air conditioning design of 12 hotel buildings in Chongqing, analyses the design energy efficiency ratio from the aspects including cold and heat sources, water circulation system, air system and whole air conditioning engineering. The results show that the cold and heat sources have prominent impacts on the air conditioning design energy efficiency ratio (EERACD), and it should be avoided in design process to make the cold and heat sources oversized, use the same pump as chilled water and hot water supply equipment without adjustment, and overuse of all-air systems, thus to improve EERACD. The surveying results show that the energy efficiency design status of hotel buildings in Chongqing is diverse from each other. Compares and analyses the difference of EERACD in these hotels, and proposes a mean value of the EERACD as the minimum energy efficiency design standard, aiming to promote enhancement of energy efficiency in public buildings.