Energy Conservation Design and Optimization of Central Air-Conditioning System Design for Xiangyuan Hotel

He Zhan-chun
Abstract:This project is about the central air-conditioning engineering of Tian Yuan Hotel,which is located in Changsha city.As the gross floors area is about(10 766.8 m~2),and the air conditioning area is about 9 228.14 m~2,and the cold load is 593 kW,we choose 2 direct burning LiBr absorption refrigeration machines: the models BZ40VⅢ and(BZ65VⅢ),with their maximal load supply,280 kW and 390 kW respectively when refrigerating.The conditioning system is divided into two different systems according to its function.The first one is for the high and big buildings such as restaurants and supermarkets;the second is for the other little rooms such as offices,bedrooms,KTV rooms.The first system adopts the complete air system,where the air-conditioning equipment deals with the supply air and the return air.The second system adopts the FCU+PAU system,where FCU system deals with the supply and the return air.The halls and the rooms which can permeate air out use natural ventilation.And almost all rooms' returning air is through the floor.The design adopts the same system to exhaust air and smoke,choosing the dual wind velocity fans,while ordinarily,it only exhausts air when the fire disaster happens.
Environmental Science,Engineering