Application possibilities of special lightning protection systems of overhead distribution and transmission lines

Mladen S. Banjanin
DOI: https://doi.org/10.1016/j.ijepes.2018.03.006
2018-09-01
Abstract:Reduction of the overhead lines back-flashover rate (BFR) after application of special lightning protection systems is analyzed in this paper. The following lightning protection systems are considered: line arresters, underbuilt wires, additional shield wire and guy wires. Partial or combined efficiencies of mentioned lightning protection systems are analyzed. Overhead distribution (35 kV) and transmission (110 kV and 220 kV) lines BFR are estimated through the semi-statistical calculation procedure as suggested in international technical documents. System equivalent circuits in the EMTP-ATP software are created with carefully chosen models and parameters of elements. Pursuant to the estimated results, conclusions about application possibilities of different lightning protection systems are given.