Experimental investigation of post and vented vapor chamber designs for high heat flux dissipation

Danny J. Lohan,Shailesh N. Joshi,Ercan M. Dede,Srivathsan Sudhakar,Justin A. Weibel
DOI: https://doi.org/10.1016/j.ijheatmasstransfer.2023.125116
IF: 5.2
2024-01-17
International Journal of Heat and Mass Transfer
Abstract:To enhance the dryout heat flux of vapor chambers over a 1 cm × 1 cm area, this study describes the testing of four different vapor chamber design architectures (each having an overall size of 50 mm × 50 mm × 5.5 mm). The designs leverage a combination of internal liquid feeding posts and evaporator vapor venting features to improve the capillary-fed boiling performance. The study provides systematic insight into increasing the dryout limit of a vapor chamber and lowering the thermal resistance by assessing the effect of each geometric feature independently. A jet impingement air cooling test facility is used to measure the total thermal resistance of the package in a representative application, while a liquid cooling test facility is used to measure the thermal resistance of the vapor chamber itself. The results show that a vapor chamber with a combination of machined posts coated with sintered wick and vapor vent features has superior performance over vapor chambers with independent features. It dissipated the highest heat flux of 589 W/cm 2 and provided the lowest total package thermal resistance of 0.28 K/W for a 1 cm 2 heat input area. The performance improvements are attributed to an improved liquid supply utilizing the porous-wick-coated machined posts and a reduction vapor egress pressure utilizing the vent features above the heater area.
engineering, mechanical,thermodynamics,mechanics
What problem does this paper attempt to address?