Abstract:We studied the effects of heat input and cooling temperature on the operational characteristics and heat transfer characteristics of flat plate pulsating heat pipes (FPPHP) using HFE-7100, HFE-7200 and HFE-7300 as working fluids. Empirical correlation equations were fitted to predict the thermal performance of FPPHP. The results showed that the start-up heat input, ultimate heat input, thermal resistance, and evaporation section temperature were positively correlated with boiling point under most operating conditions. At a cooling temperature of 20°C, the FPPHP start-up heat inputs for HFE-7100, HFE-7200, and HFE-7300 are 50 W, 70 W, and 110 W, respectively. After the start-up of the FPPHP, with the increase of cooling temperature, the flow patterns of slug flow, churn flow, annual flow, and vapor region appear successively. FPPHP has lower thermal resistance and ultimate heat input at higher cooling temperatures. At a cooling temperature of 80°C, the ultimate heat inputs of the three fluoroethers in FPPHP are 50 W, 50 W, and 90 W, respectively. In addition, it fills the gap in the empirical equations related to FPPHP and fluoroether working solutions and expands the Ku value range in the current experimental equations to 0.084.