Theoretical investigation of the influence of pipe diameter and exit channel width in welded plate heat exchanger on heat exchanger performance

Jeonggyun Ham,Yunchan Shin,Honghyun Cho
DOI: https://doi.org/10.1007/s00231-019-02733-8
2019-09-10
Heat and Mass Transfer
Abstract:In this study, to examine the effects of the changes in the inlet and outlet pipe diameters and exit channel width on the performance of a welded plate heat exchanger, a CFD (Computational Fluid Dynamics) analysis of the welded plate heat exchanger was carried out while changing the R<sub><em class="EmphasisTypeItalic">p-ch</em></sub> (ratio between the cross-section area of pipe and channel) and R<sub><em class="EmphasisTypeItalic">f-e</em></sub> (ratio between the end width of exit and front width of channel). The realizable k–<em class="EmphasisTypeItalic">ε</em> model with the non-equilibrium wall function was used. As a result, the heat exchange performance decreased slightly, but the pressure drop decreased significantly by a decrease in R<sub><em class="EmphasisTypeItalic">p − ch</em></sub> and an increase in R<sub><em class="EmphasisTypeItalic">f − e</em></sub>. In addition, the results of this study confirmed that a change in R<sub><em class="EmphasisTypeItalic">p − ch</em></sub> affects the pressure drop of inlet and outlet manifolds significantly, and a change in R<sub><em class="EmphasisTypeItalic">f − e</em></sub> affects the pressure drop of the channel and outlet manifold significantly.
thermodynamics,mechanics
What problem does this paper attempt to address?