A Study on the Analysis of Pressure Difference According to the Stack Effect of High-Rise Buildings during Fire

HyeWon Kim,InHyuk Koo,YunSeong Kim,ByeongHeun Lee,SeungHyeo Jin,YoungJin Kwon
DOI: https://doi.org/10.9798/kosham.2021.21.1.161
2021-02-28
Journal of the Korean Society of Hazard Mitigation
Abstract:As the number of high-rise buildings in Korea continues to increase, interest in the stack effect is increasing. In particular, in the event of a fire, as the indoor temperature increases, there is the problem that the stack effect increases. Accordingly, it is necessary to analyze the stack effect resulting from temperature change during a fire. In this study, by using CONTAMW simulation, the opening was opened or closed. In the case where the temperature of the fire room rises to the temperature of the growth period caused by a fire, the pressure difference in the building according to the temperature increase during a fire was confirmed. As a result, depending on whether the opening was opened or closed, the pressure difference was uniform for each layer, ranging from 0 to 100 Pa when opened. However, assuming a fire room, the pressure in the fire layer increased to approximately 250 Pa, and it was confirmed that the pressure difference varied greatly for each floor.
What problem does this paper attempt to address?