Guidance for data-center CFD (RP-1675)
Beichao Hu,James Vangilder,Mark Seymour,Dhaval Patel,Yogendra Joshi,Cheng-Xian Lin,Beichao HuJames VangilderMark SeymourDhaval PatelYogendra JoshiCheng-Xian Lin1 Department of Mechanical and Materials Engineering,Florida International University,Miami,FL,USA2 Schneider Electric,Andover,MA,USA3 Cadence Design Systems,London,UK4 George W. Woodruff School of Mechanical Engineering,Georgia Institute of Technology,Georgia,GA,USA
DOI: https://doi.org/10.1080/23744731.2024.2309125
2024-02-27
Science and Technology for the Built Environment
Abstract:This article reviews and summarizes research conducted during and related to ASHRAE RP-1675, Guidance for Data Center CFD. The ultimate objective is to provide users and vendors of computational fluid dynamics (CFD) tools with best-practice modeling advice to support greater adoption of the technology to design and operate reliable and sustainable facilities. RP-1675 identified and developed good CFD modeling practices by benchmarking CFD simulations against experimental measurements for a "laboratory data center," considering past and concurrent research, and performing additional sensitivity studies in CFD. This article provides a detailed review of the experimental and CFD work conducted during RP-1675, which focused on the modeling of computer room air handler units (CRAHs) with vertical-axis blowers located in the raised-floor plenum, and modeling perforated floor tiles, and raised-floor stanchions. This article ultimately summarizes current guidance for data-center CFD.
engineering, mechanical,thermodynamics,construction & building technology