General laws of an unexpected overvoltage in GIS in withstand voltage tests caused by breakdown

Qiang Sun,Ziwei Zhang,Dengwei Ding,Wensheng Gao,Weidong Liu,Yanpeng Ge,Fangyan Hu,Rui Tong,Jiaqi Qu
DOI: https://doi.org/10.17775/CSEEJPES.2023.09220
IF: 6.014
2024-01-01
CSEE Journal of Power and Energy Systems
Abstract:During the on-site withstand voltage tests of GIS and GIL, secondary breakdowns have been observed. However, it is not due to a design problem with the equipment itself. An unexpected overvoltage caused by the reflections and transmissions of the first breakdown wave at the wave impedance discontinuities may be the reason. To avoid similar accidents, the unexpected overvoltage in the withstand voltage tests of GIS is analyzed, and the possible overvoltage amplitude is calculated in this paper. The results show that once a breakdown occurs on the T-shaped structure in the GIS, overvoltages will be generated at some positions. Especially for the longer unbroken branch, an overvoltage must occur near the terminal. Besides, the overvoltage can indeed exceed the limits of the insulation design and cause secondary breakdowns due to its high amplitude, and thus it is extremely dangerous. Therefore, possible measures are discussed to reduce the overvoltage and avoid the secondary breakdown. Experiments and simulations are carried out, and the results verify the conclusions.
What problem does this paper attempt to address?