A Corrosion Degree Detection Method of Grounding Electrodes Considering Lightning Grounding Performance and Thermal Stability

Yihua Dan,Zhanlong Zhang,Xuemeng Wang,Yuan Jiang,Jing Wang
DOI: https://doi.org/10.1016/j.measurement.2024.115272
IF: 5.6
2024-01-01
Measurement
Abstract:Tower grounding electrodes have been buried in the soil for a long time, which is often corroded and affects the safety of the power system. Therefore, it is important to detect the corrosion degree of grounding electrodes. The existing corrosion detection methods focus on power-frequency grounding characteristics. However, some corroded grounding electrodes have good power-frequency grounding performance and insufficient lightning grounding performance. In this case, the existing methods could misjudge some grounding electrodes with insufficient lightning grounding performance as good grounding electrodes and cause electrical accidents. To solve the problems, this paper studies the corrosion degree detection method (CDDM) of grounding electrodes considering lightning grounding performance and thermal stability. Firstly, the corrosion assessment theory of grounding electrodes is given. Then, the response characteristics of corroded grounding electrodes are analyzed. Finally, the CDDM based on minimum safe diameter is proposed and verified by the case study. The results show that CDDM can accurately detect the corrosion degree of grounding electrodes, which lays a solid foundation for avoiding electrical accidents caused by grounding corrosion.
What problem does this paper attempt to address?