Removal Efficiency of Restroom Ventilation Revisited for Short-Term Evaluation

Yuyao Chen,Zhiqiang Zhai,Zhe Yuan,Guoqing He
DOI: https://doi.org/10.1007/s44213-024-00030-7
2024-01-01
City and Built Environment
Abstract:Ventilation efficiency or contaminant removal efficiency is often evaluated using the ratio between the concentrations in the exhaust air and the room air. This ratio does not truly represent the expectation of ventilation in restrooms, where dynamic airflow fields and sources are more typical. This study focuses on a short-term (10 min) pollutant removal percentage in a residential restroom featuring a dynamic airflow field, particularly with the onset of window-induced stack ventilation during toilet uses. Thirteen ventilation scenarios of a residential restroom were studied using the numerical method that was validated by a mock-up experiment. The scenarios differed in the operation of the exhaust fan and window. Results show that the 10-min pollutant removal percentage of a typical exhaust ventilation system at 10 h-1 air change rate (ACH) is only 68.5
What problem does this paper attempt to address?