Flashover Voltage Forecasting Mode of Iced Insulator Based on RBF Network

Jinying Yuan
2009-01-01
Abstract:The icing insulator is one of key problems for the security of power transmission line. Consequently, based on the test results on XZP-300 insulator in the large artifical climate,a flashover voltage forecasting model based on a radial basis function network is put forward for UHV DC insulators under complex circumstances.The inputs of the model are environment conditions such as insulator string length ,atmosphere pressure, pollution degree and iceing water conductivity, the output of the model is fashover volatage of iced DC insulator.The orthogonal least squares (OLS) algorithm is used to select the right hide layer neurons and center vectors,and the weight from hide layer neurons to output layer neurons are determined by the pseud-inverse method. The average percentage error of forcasting flashove voltage does not exceed 1%,which is in accordance with the test result and better than BP network,it is verified that the model is feasible as a new way to forecast the flashover voltage of icing insulator under complex circumstance conditions. which is of great value for providing technical references to the external insulation design and anti-icing and de-icing in China.
What problem does this paper attempt to address?