Thermal Defect of 220 Kv MOA by Infrared Diagnosis and Field Treatments Analysis

Yuantao Gu
2010-01-01
Abstract:Safety operation of metal oxide arresters(MOA) is the guarantee of power system stabilization.The thermal defect of 220 kV MOA and was introduced,which was detected by infrared diagnosis while the max temperature difference between the top unit of phase B and the others was 2.1K.The defect was confirmed when the result of de-energized tests exceed the requirement of Q/GDW2008 Regulation of test and condition-based maintenance for electric transmission and transformation equipment;and the cause was detected by MOA disassembly as resistance moisture and partial discharge.Analysis shows that the main faults of MOA are moisture ingress,resistance ageing,partial discharge and so on with the local temperature rising.The important role of infrared diagnosis for MOA Infrared thermal imaging technology which can quickly and efficiently detecting such a faults is the important method for diagnosing MOA faults.