Transient high frequency voltage protection method for ring DC microgrid with current limiting reactor

R. Huo,W. Yao,W. Huang,N. Tai,M. Yu,Y. Li,C. Fan,R. Chen
DOI: https://doi.org/10.1049/icp.2023.2184
2023-01-01
Abstract:DC line protection is the key to the development of DC microgrid technology. Current limiting reactor provides convenience for the design of DC fault protection algorithm. Aiming at the Ring DC microgrid with current-limiting reactor, this paper uses the fault transient high frequency voltage characteristics of current limiting reactor to propose a protection method based on the high frequency voltage to ground at both sides of current-limiting reactor, and uses the difference of high frequency voltage to ground at both sides of current-limiting reactor on both ends of the line after a fault to identify faults inside and outside the zone. If the impedance on the back of the line is capacitive, the protection cannot operate correctly. This problem can be solved by selecting the appropriate frequency. The simulation results show that the proposed protection method can identify the fault line and fault pole quickly and accurately, with high sensitivity and reliability, easy threshold setting and no protection cooperation between adjacent lines, and low requirements for data synchronization. The proposed method can reliably identify and select fault poles under different fault scenarios and operating modes, and has strong resistance to transition resistance.