Protection scheme for multi-terminal VSC-HVDC lines based on transient voltage

Kang JI,Neng-ling TAI,Jian LIU,Yan-hong WANG
DOI: https://doi.org/10.3969/j.issn.1673-9140.2018.01.001
2018-01-01
Abstract:The fault current of the multi-terminal VSC-HVDC has the characteristics of high rising rate and large peak value.In order to limit the fault current,the current-limiting reactor is often connected in series in a DC circuit break-er.It forms the natural boundary of DC lines,but it also leads the voltage transient process change.For an internal fault,the amplitude of high-frequency transient voltage at line side is higher than that at station side,while the fault characteristics is opposite under external fault.Based on the transient voltage features,a protection scheme for multi-terminal VSC-HVDC lines was proposed in this paper.The fast action of internal fault metallicity fault was realized by distinguishing voltage derivative rate of single-ended line side.And by the current-limiting reactor transient voltage ra-tio of each line terminal,the fault would be reliably discriminated whether it is internal or external.The simulation re-sults show that the proposed protection scheme is speedy,and not influenced by fault resistance.And it does not need the data synchronization between two terminal.