High Resistance Grounding Fault Line Selection Method for Active Distribution Network Based on GA Optimized BP Neural Network

HE Xiaolong,GAO Hongjun,GAO Yiwen,YANG Rui,LIU Junyong,HUANG Yuan
DOI: https://doi.org/10.3969/j.issn.1673-7598.2023.04.008
2023-01-01
Abstract:When the high resistance grounding fault occurs in the distribution network,the access of inverter interfaced distributed generation will inject unbalanced harmonic current into the zero-sequence network,change the distribution law of original fault characteristics,and lead to the failure of traditional high resistance fault line selection method. Considering the influence of photovoltaic power access to distribution network,GA-optimized BP neural network is proposed based on high resistance grounding fault line selection method of active distribution network by integrating various fault characteristics. Firstly,the resonant grounding system is built by Matlab/Simulink to simulate the fault zero sequence current of selected frequency wave,and the wavelet packet energy entropy and mode maximum are extracted from the system according to the wavelet packet transform and taken as data samples.Then,the data is inputted into the optimized network for training,and the machine learning model that can realize intelligent route selection is obtained. Finally,an example analysis shows that the proposed method can improve the iteration speed and training accuracy compared with the traditional algorithm,has good fault tolerance rate of line selection and certain anti-noise ability under a variety of complex fault conditions.
What problem does this paper attempt to address?