Diagnosis of Moisture Defects in Insulation of 252kv Main Transformer Bushing

Dingqian Yang,Weining Zhang,Jian Hao,Zhaoguang Du
DOI: https://doi.org/10.1109/ceepe55110.2022.9783341
2022-01-01
Abstract:Moisture is one of the main factors affecting the insulation performance of oil-paper insulating bushings, and it is of great engineering value to diagnose and analyze the damp state of oil-paper insulating bushings. In this paper, the insulation diagnosis based on the dielectric response in the frequency domain of 0.1Hz to 1kHz is carried out for the leaking oil bushings, and the characteristic value of defect judgment is extracted for comparison with the normal bushings. The characteristic value includes the average value of the dielectric loss deviation in the frequency range from 0.1Hz to 1kHz Δlg(tanδ) and real capacitance ratio KC’. The test results show that the Δlg(tanδ) of the leaking oil bushings is > 0.70, and there are multiple real capacitance ratios KC’ > 1.05. The actual disassembly inspection results show that the gaskets and cores from two leaking oil bushings are all damaged, full of discharge and wax, which means irreversible insulation degradation has occurred. Compared with the normal bushing, the dielectric loss increment of them are all more than 70%, and the capacitance change are more than 5%, which provides a reference for the field test and diagnosis of the moisture defect of the oil-paper insulation bushing.