Analysis of Transient Overvoltage in MMC-HVDC System with DC Circuit Breaker and SFCL

C. Sheng,L. Xiao,L. Ren,S. Liang,Z. Cai,X. Tan
DOI: https://doi.org/10.1049/icp.2020.0418
2021-01-01
Abstract:The difficulty in DC fault protection is the bottleneck that limits the widespread application of modular multilevel converter based high voltage direct current (MMC-HVDC) system. By installing superconducting fault current limiter (SFCL) and DC circuit breaker, the DC fault current can be limited effectively and interrupted thoroughly. However, the additional protection devices may affect the transient overvoltage of the system under fault. This paper analyses the transient overvoltage in MMC-HVDC system with DC circuit breaker and SFCL. First, a three terminal MMC-HVDC system configured with mechanical DC circuit breaker and resistive SFCL is established in PSCAD/EMTDC. Then, typical faults and key nodes of the system are summarized. Finally, through a variety of fault simulations, the maximum overvoltage of the converter and SFCL are calculated.