Attenuation characteristics of transformer vibration in typical building structures

李军,吴晓文,谢紫银,翟国庆,Hakbong Kim,卢铃
DOI: https://doi.org/10.11684/j.issn.1000-310X.2021.03.020
IF: 3.614
2021-01-01
Applied Acoustics
Abstract:In order to explore the vibration attenuation laws of 10 kV distribution transformer in residential area, the measured vibration acceleration of a transformer was converted into an exciting force, which acted on shear wall or frame buildings. The attenuation characteristics of transformer vibration in buildings were simulated through a finite element method. Results showed that the vertical vibration acceleration level (0∼ 500 Hz) of each floor caused by transformer on the first floor below ground would decline linearly with the increase of lgh, the logarithm of height from building floor to ground, when both the height of each floor and the number of floors were all same in a high-rise building with shear wall or frame structure. Their slopes were 33.26 and 24.84, respectively. The attenuation rate in shear wall building, the decrement of vibration acceleration level when lgh increased 1, was about 1.3 times that in frame building. In shear wall and frame 2020-07-09收稿; 2020-10-21定稿 ∗国家电网有限公司科技项目 (5216A019000P) 作者简介: 卢铃 (1988– ), 男, 湖北黄冈人, 博士研究生, 研究方向: 电力设施噪声与控制、监测诊断。 †通信作者 E-mail: ziyinxie@zju.edu.cn 第 40卷 第 3期 卢铃等: 变压器振动在典型建筑结构中的衰减特性 475 multi-story buildings, their slopes were 31.87 and 20.07, respectively, and the attenuation rate of the former was about 1.6 times that of the latter. It could be seen that transformer vibration attenuation rate in a shear wall building would be faster than that in a frame building when the height and number of floors were the same. When a building structure was the same, the attenuation rate of vibration in a high-rise building would be slightly higher than that in a multi-story building. In the case of 0∼ 80 Hz vibration, the attenuation rate of vertical Z-weighted vibration level in a high-rise building with a shear wall structure was about 2.4 times that of a high-rise building with a frame structure. The vibration attenuation rate of a shear wall multi-story building was about 3.7 times that of a frame multi-story building. On this basis, the single value and frequency division prediction model of the vibration propagating to different floors of shear wall and frame buildings were established, which can provide the basis for the prediction and control of indoor vibration caused by transformer.
What problem does this paper attempt to address?