A Study Of Temporary Hanged Grounding Wire Detection Scheme In Distribution Lines Maintenance Or Reconstructing Work

Jun Lu,Lefeng Cheng,Tao Yu,Kaiping Qu,Ming Liu
2015-01-01
Abstract:During the lines maintenance and rebuilding work in 10kV distribution network, at least a group of grounding wire must be hanged to the distribution lines for safe, and after the work and before recover the power service, the grounding wire must be removed entirely. It's significant to detect the grounding wires which aren't removed, then on this basis, an electromagnetic transient simulation model based on PSCAD/EMTDC platform for temporary grounding wire detection is established in this paper, in which the physical environment of grounding detection is simulated, and a detection scheme based on symmetrical three-phase signal injection method is proposed according to the simulation results, in which the voltage signal are injected into the loop circuit and three phases of current are sampled and judged in the detector device, based on threshold current value method we can judge whether a grounding wire exists. The scheme shows a better practicability in judgement of three-phase, two-phase and single-phase grounding situation, as well as the inter-phase short circuit. The proposed scheme can effectively detect the grounding wires which are not removed and thus avoid the accidents of "power recovery with hanging a grounding wire".
What problem does this paper attempt to address?