Corrosive Behavior Study Of Q235 Steel Coated With Epoxy Composites In Substation Environment

Yong Li,Jin Fu,Wei Chen,Wenjing Yang,Xueming Li,Yanjun Yin,Qihui Wang
DOI: https://doi.org/10.2991/ifmca-16.2017.86
2017-01-01
Abstract:In this work, the epoxy composite coating composited by zinc rich epoxy primer and silver epoxy enamel, was sprayed on the surface of Q235 steel. The anticorrosion of as-prepared samples in substation environment with atmospheric exposure for 18 months, and in 5% NaCl aqueous solution for 250 days were evaluated and compared, respectively. Electrochemical impedance spectroscopy (EIS) was employed to analyze the corrosive behavior of epoxy composite coating in 5% NaCl aqueous solution, the weather resistance and salt resistance were also evaluated. Additionally, the structure changes of epoxy composite coating induced by salt immersion and atmospheric exposure were characterized by fourier transform infrared (FT-IR). The results are demonstrated that the epoxy composite coating is corroded to be invalid after immersed into 5% NaCl aqueous solution for 250 days, which the impedance decreases from 3.967x10(9) . cm(2) to 9.780x10(2) . cm(2). The mechanism of corrosion is proposed that the corrosive medium gradually penetrate into the composite coating to form micro electric circuit through micro pores, resulting in the increase of porosity and corrosive rate for the composite coating. However, the impedance of epoxy composite coating in substation environment for 18 months is still 2.708x10(6) . cm(2), indicating the good corrosion resistance.
What problem does this paper attempt to address?