Use Of A Novel Electrostatic Sampler In Detecting Airborne 1legionella Pneumophila

Zhen Shi-Qi,Qian Le,Yao Mao-Sheng,Zhou Ming-Hao,Chen Lian-Sheng,Zhang Qi,Zhang Bao-Ying,Chen Xiao-Dong,Yin Li-Hong
2010-01-01
Abstract:[Objective] Investigate the efficiency of a novel electrostatic sampler in detecting airborne Legionella Pneumophila. [Methods] As a reference, BioSamplers were operated in parallel with the electrostatic sampler in the key points of the central air conditioners' system. Air samples collected were further amplified using nested qPCR for detecting Legionella pneumophila. [Results] For all the samples taken (414 L of air) by the electrostatic sampler, L. pneumophila positive rate was 12.5%. While for the samples taken (768 L of air) by the BioSampler, the positive rate was 20.8%. [Conclusion] Compared with the BioSampler under the field sampling conditions, the new electrostatic sampler obtained relatively lower L. pneumophila positive rates, which was largely due to the smaller volume of air sampled by the electrostatic sampler.