Simulation Of Em-Wave Modes Exciting Characteristics Of Partial Discharge In Gis

Junhua Liu,Yong Qian,Chengjun Huang,Xiuchen Jiang
2009-01-01
Abstract:Ultra-high frequency (UHF) method is widely used for partial discharge (PD) detection in Gas Insulated Switchgear (GIS) for the advantages of high sensitivity and the good ability of anti-disturbance which get PD information by detecting UHF EM-wave signal. Currently, most of the researches about the characteristic of EM-Waves of PD in GIS are emphasis on the EM-Wave resonance and propagation characteristic, while the EM-Wave exciting characteristic of PD haven't get attention. In this paper, the EM-wave modes exciting characteristics are analyzed by constructing the simulation model with finite difference time domain (FDTD) method. Firstly, the characteristics of EM-wave modes distribution in GIS are researched and the simulation results show that TE11(0)0, TE21(0)0 and TE31(0)0 are the dominant components of the corresponding high order mode, it can he concluded that the EM-wave signals at the positions of phi=0 degrees and phi=180 degrees will be strongest. Secondly, the relationship between EM-wave modes and PD source are studied by changing the parameters of PD sources such as PD pulse waveform and the location of PD source. The simulation results show that all the EM-wave modes of PD signal in GIS are related with the PD source while TEM mode can hardly be influenced by PD pulse width.