Experimental Research on Operational Characteristics of Pumping and Recharging Well—A Case in Shanghai

Wei SONG,Long NI,Yang YAO
DOI: https://doi.org/10.3969/j.issn.1671-1815.2017.29.013
2017-01-01
Abstract:Because of insufficient research on operational characteristics of pumping and recharging well (PRW),an experimental sandbox of single well cycling ground heat exchanger system has been used.According to the time scale of heating and air conditioning period in Shanghai,two operation modes have been carried out that experimental study on summer and winter (SW) mode & winter and summer (WS) mode.The results show that the aquifer heat loss of this experimental sand box is fast,while the heat discharge of thermal well is relatively easy under the heat release condition.However,it is difficult to extract the heat under absorption condition.In cold load dominated area,to ensure long-term reliable operation of system,assistive technology should be used to sharing the cooling load of the aquifer during the operation of PRW;it is suggested that the system first carries on the operation of the winter heat absorption condition,and the aquifer storage heat is extracted,and then the heat release is carried out in summer.Keep the lower outlet water temperature and raise the coefficient of performance (COP) of heat pump unit.