An experimental investigation of the performance of an air-source heat pump hot-water system based on saltwater energy towers

陈伟,屈利娟,汪超,俞自涛,王靖华
DOI: https://doi.org/10.3785/j.issn.1008-973X.2012.08.020
2012-01-01
Abstract:To improve the efficiency and adaptability of the existing energy tower-based air-source heat pumps, a new concept of tunable air-source heat pumps was proposed based on saltwater energy towers. A hot-water system incorporated with this new type of heat pumps was designed and constructed. The performance of the system was analyzed and compared between typical summer and winter months. Variations of the coefficient of performance (COP) of the system were presented as functions of ambient temperature and humidity, flow rate and temperature of supplying/recirculating water, make-up water temperature, and power consumption. The COPs of the entire system, heating portion, and heat pump were 1.44, 1.75 and 3.55 for summer, respectively, whereas those were 2.07, 2.33 and 3.29 for winter. The system had been operated successfully for more than 1 a and was running well below 0°C in winter.
What problem does this paper attempt to address?