Experimental Performance Analysis and Optimization of a Direct Expansion Solar-Assisted Heat Pump Water Heater

Y. W. Li,R. Z. Wang,J. Y. Wu,Y. X. Xu
DOI: https://doi.org/10.1016/j.applthermaleng.2006.08.007
IF: 6.4
2007-01-01
Applied Thermal Engineering
Abstract:A direct expansion solar assisted heat pump water heater (DX-SAHPWH) experimental set-up is introduced and analyzed. This DX-SAHPWH system mainly consists of 4.20m2 direct expansion type collector/evaporator, R-22 rotary-type hermetic compressor with rated input power 0.75kW, 150L water tank with immersed 60m serpentine copper coil and external balance type thermostatic expansion valve. The experimental research under typical spring climate in Shanghai showed that the COP of the DX-SAHPWH system can reach 6.61 when the average temperature of 150L water is heated from 13.4°C to 50.5°C in 94min with average ambient temperature 20.6°C and average solar radiation intensity 955W/m2. And the COP of the DX-SAHPWH system is 3.11 even if at a rainy night with average ambient temperature 17.1°C. The seasonal average value of the COP and the collector efficiency was measured as 5.25 and 1.08, respectively. Through exergy analysis for each component of the DX-SAHPWH system, it can be calculated that the highest exergy loss occurs in the compressor, followed by collector/evaporator, condenser and expansion valve, respectively. Further more, some methods are suggested to improve the thermal performance of each component and the whole DX-SAHPWH system.