Effects Of Ambient Parameters On The Performance Of A Direct-Expansion Solar-Assisted Heat Pump With Bare Plate Evaporators For Space Heating
Wenzhu Huang,Jie Ji,Mawufemo Modjinou,Jing Qin
DOI: https://doi.org/10.1155/2017/3082740
2017-01-01
International Journal of Photoenergy
Abstract:Research on the direct-expansion solar-assisted heat pump (DX-SAHP) system with bare plate evaporators for space heating is meaningful but insufficient. In this paper, experiments on a DX-SAHP system applying bare plate evaporators for space heating are conducted in the enthalpy difference lab with a solar simulator, with the ambient conditions stable. The independent effects of ambient temperature, solar irradiation, and relative humidity on the system performance are investigated. When ambient temperature changes as 5 degrees C, 10 degrees C, and 15 degrees C, COP increases as 2.12, 2.18, and 2.26. When solar irradiance changes as 0W m(-2), 100W m(-2), 200W m(-2), 300W m(-2), and 500W m(-2), COP of the system changes as 2.07, 2.09, 2.14, 2.26, and 2.36. With ambient temperature of 5 degrees C and solar irradiance of 0W m(-2), when relative humidity is 50%, no frost formed. Whereas with relative humidity of 70% and 90%, frost formed but not seriously frosted after 120 min of operating. Frost did not deteriorate but improved the heating performance of the DX-SAHP system. The change of relative humidity from 70% to 90% improves the evaporating heat exchange rate by 35.0% and increases COP by 16.3%, from 1.78 to 2.07.